These regulators are used to control and maintain the amount of air in VAV systems.
For correct pressure readings and for a flow rate tolerance of 5%, a straight duct with a length equal to 2/3 times the regulator diameter must be provided upstream. Otherwise, the air flow rate may vary between 10% and 20% from the calibrated value.
-Galvanised steel sheet casing;
-Dynamic Δp probe to measure and maintain the air flow rate according to the room demand;
-Galvanised steel damper with sealing gaskets;
-Operating range between 20 and 1500 Pa;
-Flow rate adjustment and control by means of a linearised motor controller;
-Self-generated and radiated noise tests according to the EN ISO 3741 Standard;
-Damper tightness test performed according to the EN 1751 Standard.
-VAV-COMPACT, AC/DC 24 V, MP-Bus, IP54
LMV-D3-M (5nm) (Standard)
-VAV-Compact, AC/DC 24 V, Bacnet MS/TP, Modbus RTU, MP-Bus, IP54 LMV-D3-MOD (5Nm)
-VAV-Compact, AC/DC 24 V, KNX (S-Mode), IP54
LMV-D3-KNX (5Nm)
ERVC single casing.
ERVC-I double casing.
When ordering, indicate the minimum and maximum air flow rates to be programmed.
Model | Minimum air flow rate |
Maximum air flow rate |
øP | S | L | C | ERVC single casing. Control signal 2...10V |
ERVC single casing. Control signal 0...10V |
ERVC-I double casing. Control signal 2...10V |
ERVC-I double casing. Control signal 0...10V |
mm | m3/h | m3/h | mm | mm | mm | mm | euro | euro | euro | euro |
125 | 53 | 445 | 8 | 0,6 | 370 | 0,8 | 520,51 | 520,51 | 550,86 | 550,86 |
160 | 87 | 725 | 8 | 0,6 | 415 | 0,8 | 533,52 | 533,52 | 565,32 | 565,32 |
200 | 138 | 1130 | 8 | 0,6 | 470 | 0,8 | 546,52 | 546,52 | 582,66 | 582,66 |
250 | 212 | 1770 | 8 | 1,2 | 540 | 0,8 | 563,87 | 563,87 | 608,68 | 608,68 |
315 | 337 | 2810 | 12 | 1,2 | 630 | 0,8 | 587,00 | 587,00 | 637,59 | 637,59 |
355 | 428 | 3570 | 12 | 1,2 | 685 | 0,8 | 607,23 | 607,23 | 662,16 | 662,16 |
400 | 543 | 4525 | 12 | 1,2 | 7 | 0,8 | 630,36 | 630,36 | 691,07 | 691,07 |