Air flow regulator for circular duct made of fire resistant plastic material (M1).
PVC casing on 80 and 100 mm diameters.
Galvanised steel casing on larger diameters.
PVC control valve.
Diameters available from 80 to 250 mm.
Air flow calibration possible during installation.
Constant flow operation for pressure range from 50 to 250 Pa.
Maximum operating temperature 60°C.
Installation takes place by inserting the regulator inside the circular duct, in both horizontal and vertical ducts.
Range 150 - 600 Pa.
all dimensions are expressed in mm
model ERDR |
d1 | d2 | L |
80 | 76 | 76 | 55 |
100 | 96 | 93 | 70 |
125 | 120 | 117 | 86 |
150 | 145 | 148 | 91 |
160 | 145 | 148 | 91 |
200 | 190 | 195 | 91 |
250 | 235 | 245 | 120 |
X: adjustable flow rate values for each model
ERDR model | flow rate m³/h | |||||||||||||||||||||||
Ø mm | low rate m³/h | 15 | 30 | 45 | 50 | 60 | 75 | 90 | 100 | 120 | 150 | 180 | 210 | 240 | 270 | 300 | 350 | 400 | 450 | 500 | 550 | 600 | 650 | 700 |
80 | 15 - 50 | x | x | x | x | |||||||||||||||||||
100 | 15 - 50 | x | x | x | x | |||||||||||||||||||
100 | 50 - 100 | x | x | x | x | x | ||||||||||||||||||
125 | 15 - 50 | x | x | x | x | |||||||||||||||||||
125 | 50 - 100 | x | x | x | x | x | ||||||||||||||||||
125 | 100 - 180 | x | x | x | x | |||||||||||||||||||
150 | 15 - 50 | x | x | x | x | |||||||||||||||||||
150 | 50 - 100 | x | x | x | x | x | ||||||||||||||||||
150 | 100 - 180 | x | x | x | x | |||||||||||||||||||
150 | 180 - 300 | x | x | x | x | x | ||||||||||||||||||
160 | 15 - 50 | x | x | x | x | |||||||||||||||||||
160 | 50 - 100 | x | x | x | x | x | ||||||||||||||||||
160 | 100 - 180 | x | x | x | x | |||||||||||||||||||
160 | 180 - 300 | x | x | x | x | x | ||||||||||||||||||
200 | 15 - 50 | x | x | x | x | |||||||||||||||||||
200 | 50 - 100 | x | x | x | x | x | ||||||||||||||||||
200 | 100 - 180 | x | x | x | x | |||||||||||||||||||
200 | 180 - 300 | x | x | x | x | x | ||||||||||||||||||
200 | 300 - 500 | x | x | x | x | x | ||||||||||||||||||
250 | 50 - 100 | x | x | x | x | x | ||||||||||||||||||
250 | 100 - 180 | x | x | x | x | |||||||||||||||||||
250 | 180 - 300 | x | x | x | x | x | ||||||||||||||||||
250 | 300 - 500 | x | x | x | x | x | ||||||||||||||||||
250 | 450 - 700 | x | x | x | x | x |
Ø mm | flow rate m³/h | euro |
80 | 15 - 50 | 25,89 |
100 | 15 - 50 | 31,07 |
100 | 50 - 100 | 31,07 |
125 | 15 - 50 | 35,21 |
125 | 50 - 100 | 35,21 |
125 | 100 - 180 | 35,21 |
150 | 15 - 50 | 52,82 |
150 | 50 - 100 | 52,82 |
150 | 100 - 180 | 52,82 |
150 | 180 - 300 | 52,82 |
160 | 15 - 50 | 52,86 |
160 | 50 - 100 | 52,86 |
160 | 100 - 180 | 52,86 |
160 | 180 - 300 | 52,86 |
200 | 15 - 50 | 79,75 |
200 | 50 - 100 | 79,75 |
200 | 100 - 180 | 79,75 |
200 | 180 - 300 | 79,75 |
200 | 300 - 500 | 79,75 |
250 | 50 - 100 | 102,54 |
250 | 100 - 180 | 102,54 |
250 | 180 - 300 | 102,54 |
250 | 300 - 500 | 102,54 |
250 | 450 - 700 | 118,07 |